Contrec 214D Batch Controller |
Contrec 214D Batch Controller Features
- Displays Batch Total, Accumulated Total and Preset
- One or Two Stage Valve Control
- Fully Programmable
- ATEX Class 1, Zone 1 Approved
- Watertight to IP67 (Nema 4X)
- Wall, Pipe and Panel Mounting
- ATEX, IECEx, CSA Approved
- CE Compliant
DC Powered with Battery Backup
Watertight Field Mounting Enclosure
Fully User Programmable
One or Two Stage Valve Control
Keyboard Operation
Intrinsic Safety
Contrec 214D Batch Controller Flowmeter Input
The 214D will connect directly to a turbine or paddlewheel with a certified IS coil or other certified IS devices that produce a pulse output, provided they do not produce a voltage, current or power that exceeds :
Ui = 24V, Ii = 20mA, Pi = 320mW
The maximum allowed capacitance and inductance of the pulser or coil, including cabling, is limited to:
Cext = 60uF, Lext = 1.5H
Output parameters on the input are:
Uo = 10.0V, Io = 9.0mA
*Note that devices such as reed switches, which can be classed as “Simple Apparatus” as defined in EN50020, may be connected to the 214D without additional certification.
Contrec 214D Batch Controller Specifications
Display
- Type: LCD display
- Batch Total: 7 digit 10mm (0.4”) high LCD (continuously powered). *Note: The Accumulated Total is displayed when the ACCUM TOT key is pressed
- Preset: 5 digit 8.5mm (0.33”) high LCD (continuously powered)
- K-factor Range: The pulses per unit of measure (eg. pulses/ gallon) is programmable in the range of 0.0001 to 999,999
- Decimal Points: Fully programmable for Total
- Frequency Range: 0Hz to 10kHz
- Signal Type: Link settable for sine wave (15mV P-P minimum), open collector, reed switch or pulse
- Interference: CE compliance
- DC Power Input: 9-28V @ 4mA maximum
Physical
- Operating Temperature: –20 to +60°C, –4 to +140°F
Enclosure
- Protection: IP67 (Nema 4X) watertight
- Cable Entry: By cable glands
- Materials: Polycarbonate and ABS
Mounting Options
- Wall: Universal wall mounting bracket
- Pipe: A galvanized metal bracket enables the 214D to be attached to a 51mm (2”) vertical or horizontal pipe
- Panel: Two mounting brackets supplied Turbine Meter: Bottom and rear mounting stems are available for mounting the 214D directly on turbine flowmeters which have a 1” NPT or BSP boss
Battery Backup
- Type: 2 x Lithium battery packs
- Function: The batteries will provide backup power for the instrument if no DC power is available. The batteries will not power the sensor (if power is required) or solenoid outputs
Outputs
- Type: 2 x solid-state relay outputs suitable for driving DC solenoids or external relays. The outputs provide for one or two-stage control of the flow
- Switching Power: 200mA, 30Vdc maximum
- Saturation Voltage: 0.8Vdc across outputs when in the “on” state
- Isolation: Both outputs are separately isolated
Download:Data Sheets