Kobold DOR Insertion Paddle Wheel Flowmeter/Monitor |
Specification
- Measuring range: 0.25 - 6300 l/s ... 0.4 - 49000 l/s
- Flow velocity range: 0.3 - 10 m/s
- Connection: R 1½, R 2, 1½" NPT, 2" NPT male thread for pipe sizes DN40 ... DN2500
- Material: stainless steel
- pmax: 80 bar
- tmax: 150°C
- Linearity: ±1.5 %
Kobold DOR Applications
- HVAC: Hot and Chilled water, Fire system and thermal energy monitoring
- Municipal: Water distribution, water management and water treatment
- Irrigation: Water management
- Water treatment: Chlorination, de-salination and mechanical filtration plants, chemical injection systems
- Refineries: Primary flow additive injection, fire and cooling systems
- Power generation: Boiler feed water, steam condensate, process water and water balancing
- Chemical: Process & cooling tower water, chemical and water batching
- Others: Cement manufacturing, diesel fuel transferring, flow testing, fire truck and hydrant flow monitoring, food processing, pulp/paper, mining
Kobold DOR Specifications
- Velocity measuring range (linear):
0.3...10 m/s equates to approx.
0.25...49,000 l/s in DN40 to DN2500 pipes;
0.15...10 m/s when using the linearisation function of electronic type ZOK-Z3 or ZOE - Linearity: ±1.5% with well est. flow profile
- Repeatability: ±1% of f. s. at factory conditions and optimal straight runs
- Max. pressure: 80 bar
- Temperature range: -40…+100°C standard, see max. allowable medium temperature table for other options and restrictions
Material
- Body: stainless steel 1.4404 (316L)
- Rotor: PVDF or PEEK (depending on model)
- Rotor shaft: stainless steel 1.4404 (316L)
- Bearing: graphite/PTFE
- Seals:
FPM (standard): -15…+200°C
NBR (Nitril): -65…+125°C
Electronics
- Output frequency at max. velocity: 220...240 Hz (hall effect and voltage output), 73...80 Hz (reed switch output)
- Supply voltage: see electrical output specifications and electronics comparison table
- Electronic features: see data sheet ZOK (only available as remote version)
- Wiring (standard): 5 core, screened cable, length, 1 m (DOR-52), 1.5 m (DOR-42)
- Transmission distance: 1000 meters maximum
- Protection class: IP68 (cable connection)
- Straight piping requirement: Minimum: 10xd (upstream), 5xd (downstream)
- Optimal: 25xd (upstream), 10xd (downstream)
- Weight: (approx., without electronics): 1.6 kg (DOR-4), 2.5 kg (DOR-5)
Electrical Output Specifications
Hall Effect Sensor Output (FX, NX, QX)
The Hall Effect Sensor is a high resolution solid state 3 wire device providing an unsourced, open collector, NPN transistor output. The term "unsourced" means that no voltage is applied to the output from within the flowmeter. It must be pulled to a 'high' or 'on' state by between 5-24VDC supplied from an external source, typically the receiving instrument.
The pulse output between signal and -0V is a voltage square wave with the high level being the DC voltage available at the open collector and the low level being -0V. The receiving instrument must incorporate a pull up resistor (typically greater than 10kΩ in most instruments) which ties the open collector to the available DC voltage level when the Hall sensor is not energized. When energized the open collector output is pulled to ground through the emitter (-0V). Power supply: max. 5-24 VDC, max. 20 mA
Voltage Pulse Output (FX)
A self generating 2 wire voltage pulse output with 1.5 V voltage spike of approximately 10 microseconds duration is generated with no dependence on rotor speed.
Reed Switch Pulse Output (RX)
The reed switch output is a two wire normally open SPST voltage free contact ideal for installations without power or for use in hazardous area locations (simple apparatus) when Intrinsically Safe (I.S.) philosophy is adopted.
Note: when using the reed switch output the liquid temperature must not change at a rate greater than 10ºC per minute. In general the reed switch life will exceed 2 billion actuations when switching less than 5VDC at 10mA. Power supply: max. 30 VDC, 200 mA
Quadrature Pulse Output (QX)
Two Hall Effect sensors arranged to give separate outputs out of phase with one another. The Quadrature output is typically suited to ensure output signal integrity or to measure bi-directional flow. Power supply: max. 8-24 VDC, max. 20 mA
NPN Inductive Pick-up (EX)
Inductive pick-up with non-magnetic rotor for applications with high ferrous content liquids. Output is 3-wire NPN, 5-24 VDC, 20 mA max.
Download Datasheet: Kobold DOR Insertion Paddle Wheel Flowmeter/Monitor